Archived source flow
Technical notes
Client and command handling
The code connects to a configured server, sends a status request and parses update flags. A nonzero parsed sample-rate value gates the selected chlorine, phosphate, temperature and refill calls before a report is sent. It is an HTTP client, not a demonstrated browser dashboard.
Timing and initialization
Relay pin setup is defined in the relay module but is not called by the selected main sketch. Pump timing is serviced only through the refill-pause helper; the 100-second loop delay and other paths can leave it unserviced. The helper can also permit dispensing before pump completion.
Incomplete measurements and transport
The filled-cuvette flag is not updated from a sensor. Chemistry and particle report fields remain placeholders, and transmitted regulator/pump flags are fixed values. Server settings are blank and the field parser lacks bounded missing-field handling. Build, server integration, wet testing and measurement accuracy are unverified.